IEC 61034 3M Cube Smoke Density Tester

Product Description

IEC 61034 3M Cube Cable Smoke Density Tester


   Introduction:   

3 Meter Smoke Density Tester is the testing equipment measuring the smoke generated when the cable or optical cable is placed horizontally and burn under definite fire resource in the specified condition (3m3 chamber required by IEC61034). This equipment is important to measure the smoke generation from the value of light source penetration through the smoke generated when the cable exposed to the specified standard fire source (ethanol 90±1%, methanol 4±1% and distilled water 6±1%) 1L±0.01L is burned. 



   Standard:   

IEC 61034 - 1 & 2

- Measurement of Smoke density of cables burning under defined condition

- part 1 : Test apparatus

- part 2 : Test procedure and requirements

BS 6853

- Code of practice for fire precautions in design and construction of passenger carrying trains



   Feature:   

1.  Chamber internal area is 3000mm±30mm and it’s structured as Cubic Enclosure with appropriate fixed iron frame angle.

2.  It's configured with a door with test glass windows and in both faces of the opposite side there’s a sealed transparent window (minimum 100mmX100mm) with a horizontal light measure system that allows light penetration.

3.  Designed to prevent direct sunlight exposure and severe weather change in Enclosure.

4.  Photocell and Light Source are located in the middle part of both windows of the wall surface in the opposite side to avoid physical contact.

5.  A lamp to provide regular light is installed.

6.  Two types of auto Filter system (Carrusel) are installed to automatically calibrate the transmissivity of light.

7.  The reduction of light by smoke is measured using Photocell.

8.  In order to verify accordingly the intensity of radiation to measure light change by self-emission, the equipment has been designed to fit various kind of filter in the Light Source.   

9.  Support system to allow separate fitting of Light Source and Photocell in the outer wall.

10.  The Light Source is a halogen lamp with a clean crystal lamp and tungsten filament.

11.  Average power : 100W, Average voltage: DC12v, Average velocity of light : 2000 lm~3000 lm, and Average color temperature : 2800K~3200K.

12.  The Receptor Photocell is selenium or silicone type and has a spectrum reaction conform to Photopic Observer (similar to a human eye) of the International Commission on Illumination (CIE).

13.  A heating system is installed within the cube to swiftly match the standard temperature (25℃±5℃) in the initial test.

14.  We seek tester's safety and convenience through an Auto ignition system.



Test Result:

- Flameout time(min)

- Time to max Ao

- Min light transmittance (%)

- Add photo feature of carbonization area


   Specification:   

Frame dimension

3,000(W) × 3,000(D) × 3,000(H)mm
Frame material Stainless Steel SUS 301
Transparent sealed window 100 × 100 mm
Foundation Fixed Fixture unit
Light Source Power DC12V, 100W
Light Source Focus Angle 48˚ - 4.5˚
Light Source Focus Intensity 1:20
Photo Cell Diameter Ø45 mm
Photo Cell Cell Type Selenium Cell
Exhaust Blower Fan Flow 7 m3/min ~ 15 m3/min
Exhaust Blower Size 246(W) x 220(D) x 205(H) mm
Exhaust Blower Material Stainless Steel (Inner Fan)
Exhaust Blower Power AC220V, 60Hz, φ1, 210W
Exhaust Blower Flow Rate(max) 8.0m3/min
Auto Control Damper for Exhaust
Power AC220V, 60Hz
Torque Normal 300kg.f.cm , max 480 kf.f.cm
Rotation Angle 0~90˚ ± 5˚
Wind Velocity ≤ 15m/sec
Control Rack Dimension 730(W) X  650(D) X  1,400(H)mm



   Welcome to contact us:  

Contact Person: Kiana Feng

Whatsapp/Wechat: +86 15922982738

Mobile: +86 15922982738

Fax: +86-23-62940030

Email: gold20@hy-industry.com

Product Inquiry

Burning Behaviour of Bunched Cables IEC 60332-3

UL1581 Vertical Wire Flame Tester

IEC 60331 Wire and Cable Fire Resistance Test and Hammer Test Machine

IEC 60331 Fire Resistance Tester for Wire And Cable

ISO 4589-2 Limited/ Limiting Oxygen Index Tester, ISO 4589-3 Elevatd-Temperature Oxygen Index Tester

Electric Cables Halogen Acid Gas Release Testing Apparatus, Cable Corrosion Tester IEC 60754-1, 2

IEC 60332-1 Flame Propagation Test for Single Cable