Smoke Density Chamber ASTM E662, BS 6401

Product Description

Smoke Density Chamber ASTM E662, BS 6401


Description:

The working principle of the NBS smoke density test chamber is to calculate the specific optical density by measuring the light transmittance of the smoke (in %) using the built-in optical system of the test chamber. The minimum light transmittance is usually used to calculate the maximum specific optical density Ds.

The formula is: Dsmax=132Log10(100/Tmin).

Tmin is the minimum light transmittance during the test.


The NBS smoke density test chamber consists of the following components:

The test chamber, with internal dimensions of 914mm x 914mm x 610mm, has good corrosion resistance.

Built-in optical measurement system.

Radiant heat source.

Data acquisition system.

Operating software.


In the smoke density test, the sample is mounted horizontally/vertically in the test chamber and its upper surface is exposed to a radiant heat source of a specific irradiance (up to 50 kW/m²). The generated smoke is collected in the test chamber and the attenuation of the light beam passing through the smoke is measured by the built-in photometric measurement system in the test chamber. The data and results are collected and calculated by the software.


Main feature:

  • Integrated body and 19” analysis rack (Saving space).

  • 17” touch screen panel type PC for the whole control and automatic testing.

  • Air cylinder type movement to load sample or automatically open the up/down  vent(highly resistant to pollution from test).

  • Coating of the test chamber convenient in cleaning and resistant tochemicals.

  • Lock designed to close the chamber door at a time.

  • Indication of transmission rate and smoke density with improved accuracy.

  • Chamber preheat system to facilitate test with more accuracy.

  • Safety blow-out panel system to protect user when pressure is sharply increased during test.

  • Port, heated filter, and heated line to measure toxic gases.

  • Manometer gauge with increased accuracy by using the MFC (Mass Flow Controller) and DPT(Differential Pressure Transducer) enabling auto leakage test.

  • Portable water cooling system without need for waterworks and plumbing when using the Heat Fluxmeter (for ISO 5659).

  • Load cell with increased accuracy to measure mass loss rate in ISO 5659 test.

  • SB 2005 DAQ(Data Acquisition) Program to control the use of touch screen panel PC.

Test result:

  • Laboratory Information

  • User’s CI

  • Specimen Conditions

  • Time from start of test, t(s)

  • Transmission(%) and specific optical density, Ds

  • Maximum Ds and time to maximum Ds

  • Correction Ds

  • Current range setting and filter position

  • Current mass(g) for ISO 5659


Specification:

Size

1,600mm(w) × 820mm(D) × 2,150mm(H)

Power

220 V AC, 60 Hz, 15 A

Weight

about 350 kg

Exhaust

50 l/s

Utilities

Compressed Air, Propane Gas, Personal Computer, Dust Collector


Product Inquiry

Wire and Cable IEC 60332-3-10 EN 50399 Bundle Combustion Heat Release Tester

IEC 60331 Circuit integrity Tester Cable BS 6387 Fire Resistance Test Equipment BS 8491

BS 6387 Cable Fire-resistant Impact And Water Spray Test Equipment for LSZH FR Cables

ISO 4589-2 Limiting Oxygen Index Tester ASTM D 2863 for Plastic Insulation Materials

XLPE Cable Insulation Slicing Machine