EN ISO 1182 / EN 1182 Test Methods for Non-Combustibility of Building Materials

Publish Time: 2019-09-27     Origin: Site

EN ISO 1182 / EN 1182 Test Methods for Non-Combustibility of Building Materials

Non-combustible materials refer to those who do nor catch fire, smoke, or burn when they are exposed to flame or high temperature. It includes all natural materials (stones, sands, clays,etc.) as well as artificially made inorganic materials and metal materials used in construction.

Attention --- EN ISO 1182 / EN 1182 Test Methods for Non-Combustibility of Building Materials 

1. Temperature rise

In the ℃ unit, the furnace temperature rise and sample temperature rise of each sample were calculated by the following formula.

a) Temperature rise in the furnace      △Tf=Tf(max)-Tf(final)

b) Temperature rise of the sample center      △Tc=Tc(max)-Tc(final)

c) Temperature rise of the sample surface      △Ts=Ts(max)-Ts(final)

T(max) is the highest temperature and T(final) is the final temperature at the end of the test

The arithmetic mean of the furnace temperature rise, the sample center temperature rise, and the sample surface temperature rise for each sample was recorded and calculated.

2. Flame

The flame records the sum of the duration of the flames of each sample, in units of S.

       Record and calculate the arithmetic mean of the duration of the flame for each sample.

3. Quality losing

The mass loss of each sample was recorded and calculated as percentage of the initial mass of the sample.

Record and calculate the arithmetic mean of the mass loss for each sample.

Assessment of results --- EN ISO 1182 / EN 1182 Test Methods for Non-Combustibility of Building Materials 

According to EN ISO 1182, the flammability or incombustibility of the material is assessed. The assessment is based on the following:

       The average temperature rise in the furnace should not exceed 50, and the average duration of the calculated continuous flame should not exceed 20s.

       After cooling, the average mass loss should not exceed 50% of the average initial mass.

 